Design Requirements : 供应GXT3-10000RT230 CT 医疗设备** Model Rating 9000W/10000VA Output Load Capacity 220 / 230 / 240 Internal Battery Valve-regulated, non-spillable, lead acid cells. Battery Reserve Time Minimum 3 minutes with an ambient temperature of 25°C (77°F). Battery Recharge The UPS shall contain a battery charger designed to prolong battery life. Recharge time for UPS internal batteries shall be 3 hours maximum to 90% capacity after a complete discharge into full load. Frequency The UPS shall auto-sense mains frequency of 50Hz or 60Hz when first powered up and shall use this frequency as the default output frequency. Mains Power Factor >0.99 lagging at rated load. Mains Output, UPS Inverters : Voltage Configuration 50Hz, single-phase, 2-wire-plus-ground. Voltage Regulation L-N: ±3% steady state. Frequency Regulation ±3.5Hz synchronized to mains. Frequency Slew Rate 1.0Hz per second maximum Load Power Factor Range 0.65 lagging to 1.0 (unity) Voltage Distortion Sinusoidal Waveform; ≤3% total harmonic distortion (THD) into a ** linear load; ≤5% THD into a ** non-linear load with a crest factor ratio of 3:1. Voltage Transient Response ±7% on-line or Battery mode for 0-100-0 % loading of the UPS, ±4% on-line or Battery mode for 20-100-20 % loading of the UPS. Transient Recovery Time To nominal voltage within 166 milliseconds. Efficiency 92% AC-AC Accessories : RMKIT 18 32 Rackmount Kit for GXT3